Cut out (eastern) stringer details

This diagram and chart show engineered unsupported stringer lengths for Ply-Lam used as an eastern (cut out) stringer.

The thickness (W) and effective depth (ED) of the stringer are adjusted to suit the required unsupported length. Lengths are those permitted by the Alberta Building Code.

Diagram of a cut out stringer showing thickness W and effective depth ED
Cut out stringers, standard Ply-Lam. All measurements in inches.
Product codeThickness (W)Effective depth (ED)AB code permitted unsupported length
Spruce 2x12, cut out, 5.25 in remaining1.55.2599
Spruce 2x10, cut out, 3.5 in remaining1.53.569
PL3 C 3.51.1253.555
PL3 C 5.251.1255.2578
PL3 C 8.6251.1258.625135
PL4 C 3.51.53.560
PL4 C 4.6251.54.62580
PL4 C 5.251.55.2586
PL4 C 8.6251.58.625148
PL6 C 3.52.253.571
PL6 C 4.6252.254.62595
PL6 C 5.252.255.25107
PL6 C 8.6252.258.625177
PL8 C 3.533.576
PL8 C 4.62534.625101
PL8 C 5.2535.25114
PL8 C 8.62538.625188

Shaded rows are solid spruce, shown for comparison.